VCBA S2 VERSION 4.xx SOFTWARE MANUAL REV 3
75
NOTE
For the 1-second timing window, the timing resolution is ±50 micro-
seconds
For the 10-second timing window, the timing resolution is ±500 micro-
seconds
For the 20-second timing window, the timing resolution is ±1.0
milliseconds
7. Select the trigger type from the “Trigger Type” options (Internal or External).
8. From the “Insertion Resistor” radio group, select the desired insertion resistance value.
Make sure the “Dynamic Resistance” option is NOT checked.
9. Click on the “OK” button. The following window will be displayed:
10. A 5-second timer will count down, and then the test will be initiated. A sequence of
status messages will be displayed, and when the test is complete, the results will be
displayed in the VCBA S2 software. The test record will also be saved in the location
selected in step 4.