REV 3 VCBA S2 VERSION 4.xx SOFTWARE MANUAL
34
4.9 Manually Overriding Contact Time/Resistor Contact Time or Contact Wipe
You can override the calculated Contact Time, Resistor Time, or Contact Wipe readings in the
tabulated test results. This is a useful feature for situations where a manual calculation is
preferred. For example, in the figure below, the calculated CLOSE time (61.600 ms) for channel
2 can be overridden with the preferred time (63.118 ms):