OPERATING INSTRUCTIONSfor theVBT-80PVacuum Bottle TesterVanguard Instruments Company1520 S. Hellman Ave.Ontario, California 91761TEL: (909) 923-9390 J
Operating Procedures VBT-80P94.0 VBT-80P SPECIAL FEATURES4.1 VBT-80P LCD Contrast ControlThe VBT-80P LCD is back-lighted for viewing in low light con
Operating Procedures VBT-80P105.0 VBT-80P CABLE CONNECTIONAlways ground the VBT-80P before connecting any cables. Use the ground cable provided witht
Operating Procedures VBT-80P116.0 OPERATING PROCEDURES(Refer to tables 3 through 8)WARNINGAlways connect the VBT-80P ground to the substation ground
Operating Procedures VBT-80P12Table 3 Run Test Procedure (Continued)STEPACTION DISPLAY3-7Press the “ENTER” key to continue.3-8Press and hold the “ARM
Operating Procedures VBT-80P13Table 3 Run Test Procedure (Continued)STEPACTION DISPLAY3-15Press key #1 to save the test record. Thetest record is sav
Operating Procedures VBT-80P14Figure 5 Typical VBT-80P Test Report
Operating Procedures VBT-80P156.2. Enter Test Record ID ProcedureThis procedure allows the user to enter the equipment identification information to
Operating Procedures VBT-80P16Table 4 Enter Test Record ID Procedure (continued)STEP ACTION DISPLAY4-8Enter the utility MODEL name using thealpha-num
Operating Procedures VBT-80P176.3 Restore Record ProcedureThis procedure describes how to restore a test record stored in VBT-80P’s Flash EEPROM towo
Operating Procedures VBT-80P186.4 Review Record ProcedureThis procedure allows the user to view or print a test report residing in the VBT-80P’s work
Operating Procedures VBT-80P1SAFETY SUMMARYFollow Exact Operating ProceduresAny deviation from the procedures described in this operator’s manual may
Operating Procedures VBT-80P196.5 Print/View Test Record Directory ProcedureThis procedure describes the steps to print or view the test record direc
Operating Procedures VBT-80P20Table 7 Print Test Record Directory (Continued)STEP ACTION DISPLAY7-7Press the “UP” key to view the first record’sinfor
Operating Procedures VBT-80P216.6 Erase Test Record ProcedureThis procedure describes the steps to delete one or all of the test records stored in th
Operating Procedures VBT-80P226.7 Set VBT-80P Real Time ClockThis procedure describes the steps to set the VBT-80P real time clock.Table 9 Set Time P
Operating Procedures VBT-80P231520 S. Hellman Ave., Ontario, CA 91761, USAPhone 909-923-9390 Fax 909-923-9391www.vanguard-instruments.comVBT-60/80 Au
Operating Procedures VBT-80P2Table of Contents1.0 INTRODUCTION ...
Operating Procedures VBT-80P3List of FiguresFigure 1 High voltage cable...
Operating Procedures VBT-80P41.0 INTRODUCTION1.2 General DescriptionThe VBT-80P is a lightweight DC vacuum bottle tester made by Vanguard Instruments
Operating Procedures VBT-80P5Figure 1 High voltage cableFigure 2 High Voltage return cable
Operating Procedures VBT-80P62.0 VBT-80P SPECIFICATIONSVBT-80P specifications and leading particulars are listed in Table 1.0Table 1.0 VBT-80P Specif
Operating Procedures VBT-80P73.0 CONTROL AND DISPLAY3.1 VBT-80P Front PanelThe VBT-80P controls and displays are shown in Figure 3. Pointing leader l
Operating Procedures VBT-80P8Table 2.0 Functional Description of VBT-80P Controls and DisplayFigure 1Index #Adjacent Panel Marking Functional Descrip